Preventing transformer explosions

January 8, 2015 - 06:46
Article from Gemini, SINTEF

Technology used in the crumple zones of cars can avert serious explosions in transformers, believe researchers.

A Norwegian transformer station in Skien suffered an explosion in June 2000, causing a fire and a serious oil release. (Photo: Mads Aas, Statnett)

“Transformer failures have cost human lives when things have gone seriously wrong,” says Håkon Nordhagen, a materials specialist.

Large oil filled transformers are found in all power and switching stations, as well as in many large buildings. If an internal short-circuit occurs, an electrical arc, gas formation and pressure increase will be the result.

According to Nordhagen, the likelihood that Norway could experience major explosions caused by short-circuits of this sort is low. But precisely because lives can be lost and property damaged if they do occur, he and his colleagues now want the electricity supply sector to adopt safety measures used by vehicle manufacturers.

“Today, transformers are installed in stiff steel tanks. The risk of explosions can be reduced if the industry changes to “soft” housings that absorb energy in the same way as modern car bodies,” he says.

Pilot project underway

“However, the stiffness that is usually incorporated has an unfortunate side-effect,” Nordhagen points out.

On one hand, the transformer tanks are able to withstand more pressure than they could have done without the reinforcement, on the other, the extra stiffness means that they cannot expand when the electric arc is burning, causing the pressure in the oil and gas to rise dramatically.

High internal pressure is undesirable for many reasons, says the scientist: “Combustible gases and oil can leak out of gaskets and penetrators, which may ignite fires or explosions. Moreover, stresses occur within the material of the tank, increasing the probability that it will rupture," says Nordhagen.

"And if this happens, bolts, hatch-covers and similar components may be slung out with great force, depending on how high the internal pressure is.”

This is why Nordhagen and his colleagues are so keen on developing an alternative “bodywork” solution.

Energy-absorbing tanks

Car bodywork is designed with soft zones that absorb energy from collisions by crumpling. The  idea is to design transformer tanks in such a way that they expand when their internal pressure increases, without risking that major rises in tension and weak points in their material occur as a result of the expansion.

If such an expansion is allowed, there will be more time available for the transformer to be disconnected from the grid before rupture occurs.

"It is perfectly possible to achieve this, while at the same time ensuring that the housing is stiff enough to withstand transport stresses and the vacuum treatment,” says the researcher.

The aim of the recently launched transformer safety pilot project is to pave the way for a large-scale competence-building main project.

“With better knowledge and new mathematical models, we will be able to observe the relationships between the physics of electric arcs, the transformer tank and the electrical protection system. This will offer us new prospects of modelling safe and reliable solutions,” says Nordhagen.

Country
Standard tank vs energy-absorbent tank

In the laboratory, SINTEF produced a short-circuit in a 200 kVA oil-filled distribution transformer.

  • In the first experiment, the transformer was installed within a standard tank (left). In the second, it was mounted in an energy-absorbent tank inspired by modern vehicle design concepts.
  • In order to demonstrate just how much the new concept can tolerate, the scientists induced a much higher short-circuit current than is realistic for this type of transformer.
  • In the traditional tank, one of the walls of the housing ruptured as a result of the rise in pressure caused by the short-circuit. The gases produced by the short-circuit and the oil aerosol then caught fire.
  • The tank with the new design did not leak. Just as expected, its corrugated walls absorbed the expanding volume of gas.
Transformer accidents in Norway

The most serious accident was caused by an internal short-circuit in one of the main transformers at Tonstad power station in Sirdal in Vest-Agder County in 1973. Three people lost their lives.

Fires and explosions in transformers still occur on a regular basis.

Some of them are due to faults in housing penetrators, and happen even though the housing has not ruptured.

In other cases, faults in the internal insulation have led to pressure rises that have cracked the transformer tank. Lightning, ageing components and cable breaks or breaks in earthing caused by excavations are among the causes of the faults (short-circuits) discussed here.

Source: SINTEF Energy Research